Composition and operation of dosing device:
Dosing system device components: Dissolved tank, stirrer, metering pump, level gauge, electrical control cabinet, pipe, valve, distributor, safety valve, regulator, pressure gauge, check valve, rack, etc. composition.Waste water Treatment System;
The concentration of the drug should be adjusted according to the water quality and the effluent quality.Dissolved coagulant aid and coagulant agent should be used along with random, otherwise it will effect the treatment effect of the agent, effecting the quality of the effluent.
Dissolved uneven, agglomerated agents can not be used, by using these agents dosing pipe and flow meter will block, resulting in poor chemical.
Before starting the metering pump, open the inlet and outlet valves of the pump before and after the pump, start and close the isolation valve between the metering pumps.
In operation, such as working pump failure should be cut off the working pump power, open, close the corresponding valve, start the standby pump, continue to dosing.
Should be regularly on the level gauge for sewage, cleaning filters often visit the dissolved tank level changes, and timely replenishment solution.
In order to ensure the quality of the effluent water, under normal circumstances, the coal water treatment system starts a set of water-making equipment (1 wastewater lifting pump, 1 coagulant dosing pump,
1 coagulant dosing pump and 1 high-efficiency purifier) Another set of water equipment is available as a backup.
Under normal circumstances, the frequency of the coagulant dosing pump is set to 20HZ, and the frequency of the coagulant dosing pump is set to 50HZ. If the actual water quality of the turbidimeter is unqualified, another coagulant can be activated. The chemical pump increases the amount of the coagulant.
After the turbidity decreases, gradually reduce the other coagulant dosing pump to 0HZ (stop the other coagulant dosing pump).
In order to improve the detection accuracy of the turbidity meter, the turbidity meter is required to send electricity before the start of the water-making work, and the power is turned off after the water-making work is finished. Which high-efficiency purifier is used to turn on or off which set of high-efficiency purifiers corresponds to turbidity. When the data displayed by the turbidimeter is found to be highly deviated from the
test data of the turbidity meter outlet sample in the laboratory, the thermal control professional of the maintenance department should be contacted in time for verification.
In order to avoid the leakage of the valve, effecting the dosage of the coal-containing wastewater and the quality of the effluent, under normal circumstances, when starting a coagulant dosing pump and a coagulant aid dosing pump, another coagulant should be added. The outlet manual valve of the pump and coagulant dosing pump is closed (Note: Open if another dosing pump is required